Our online store is currently under development and only contains a small amount of our available products. We are progressively adding our items to this store. If you are unable to find what you need, please contact us directly with details of your requirements and return regularly to view any new additions.

Simex SWE-N55L Loop-Powered LED Indicator

$465.00

SKU: N/A Category: Brand:

Description

Datasheet: Simex SWE-N55L

Code Description

Buy online for small quantities. For large quantities, projects and repeat business send a quotation request to: sales@birkettcontrols.com.au

The SWE-N55L is a low-cost, loop-powered digital indicator housed in a compact IP65 wall-mount case, designed for local display of a single 4-20 mA process signal. The measurement input doubles as the device’s power supply, so no separate supply wiring is needed. Built-in overload protection safeguards the internal electronics, and the device can recalculate the incoming current using linear, square, square-root, or a fully user-definable characteristic (up to 20 points).

Results are shown on a bright 4-digit red LED display, with detection and visualisation of peak values. An optional single bistable relay output (30V/500mA) can drive an indicator lamp or audible alarm for simple signalling (not intended for control duties). All parameters are freely programmable using the optional SIR-15 infrared remote controller, without needing to open the enclosure.

Delivery time for non-stocked configurations is typically 4–6 weeks.

To order a configuration not included in the above list or for application advice, send your request to: sales@birkettcontrols.com.au or contact us for more information on 02 9560 8593

Typical Application Areas:

Local, low-cost indication of a single 4-20 mA loop signal wherever a compact wall-mounted display is needed – alongside field transmitters, at remote monitoring points, or as a simple peak-value readout for process operators. The optional relay output suits basic lamp or audible alarm signalling where a full controller isn’t required.

Additional information

Power Supply

loop-powered from the 4-20 mA measurement input, min. current 3.5 mA, max. voltage drop 7V

Display

LED, red, 4 x 13 mm high

Displayed Values

-999 to 9999, with decimal point

Input

4-20 mA current, overload-protected, input current limited to approx. 50 mA

Accuracy

0.1% @ 25°C ± one digit

Stability

50 ppm/°C

Output (option)

1 x bistable relay, 30V/500mA, min. switching delay approx. 4 sec.

Data Memory

non-volatile EEPROM

Operating Temp.

0°C to +50°C (standard); -20°C to +50°C (option)

Protection

IP 65

Case

wall mounting, polycarbonate

Connections

gland M16x1.5 (standard); M12 5-pin socket + straight cable plug (option)