Skip to content
Our online store is currently under development and only contains a small amount of our available products. We are progressively adding our items to this store. If you are unable to find what you need, please contact us directly with details of your requirements and return regularly to view any new additions.

Simex SPP-94 Flow Meter, Batcher & Totalizer with 4-20 mA Input

Price range: $770.00 through $832.00

SKU: N/A Category: Brand:

Description

Datasheet: Simex SPP-94

Code Description

Buy online for small quantities. For large quantities, projects and repeat business send a quotation request to: sales@birkettcontrols.com.au

The SPP-94 flow meters are designed to work with flow transducers equipped with an analogue (0/4-20 mA) output. They measure the instantaneous flow value and record the total flow of media such as liquids, gases or loose materials, with a total flow indication for long operating periods. The built-in batcher function suits the SPP-94 to industries such as food, pharmaceutical, and paint and varnish production.

The relay or OC control outputs can be programmed to act on the instantaneous flow value, batcher or total flow value, and the meter can additionally be fitted with an analogue output (active current, passive isolated current or active voltage). A 24Vdc output is provided to power the flow transducer, and the meter can be configured with the local keyboard or free S-Config software via the RS-485 (Modbus RTU) communication port.

Delivery time for non-stocked configurations is typically 4–6 weeks.

To order a configuration not included in the above list or for application advice, send your request to: sales@birkettcontrols.com.au or contact us for more information on 02 9560 8593

Typical Application Areas:

Panel-mounted flow rate indicator, totaliser and batch controller for flow meters with 4-20 mA outputs (for example electromagnetic or vortex flow meters) measuring liquids, gases or bulk solids. Typical uses include batching and dose counting in food, pharmaceutical and chemical plants, and flow and total retransmission to PLC or SCADA systems.

Additional information

Power Supply

85~260 Vac/dc or 24 Vac/dc (19–50 Vdc / 16–35 Vac) or 12 Vac/dc

Load

6.5 VA / 6.5 W (supply dependent)

Switch Rating

Relay = 1A, 30 Vdc / 250 Vac; OC = 30 mA, 30 Vdc, max 100 mW

Analogue Output

Active current 0/4–20 mA; Passive isolated 4–20 mA; Active voltage 0/1-5V, 0/2-10V (optional, with 2× REL/OC)

Construction

NORYL – GFN2S E1, panel mounting

Protection

IP 65 (front, optional integrated frame for panel cut-out sealing); IP 20 (case and connections)

Max. Temperature

50°C (standard); optional −20°C to +50°C

Outputs

0, 2 or 4× REL/OC; or 2× REL/OC + 1× analogue output (multiple configurations available, refer to datasheet)

Display

LED, 6 × 13 mm, red, 6 digits (0–999999) with configurable decimal point

Inputs

1× current input 0–20 mA or 4–20 mA + 1× programmable binary input (24 Vdc)

Accuracy

0.1% @ 25°C ± one digit (0–20 mA range); stability 50 ppm/°C

Power Supply Output

24 Vdc, max. 100 mA (for powering sensors / transmitters)

Dimensions

96 × 48 × 100 mm (case); 90.5 × 43 mm (panel cut-out)

Communication

RS-485, Modbus RTU, 1200–115200 bit/s